V440C2 IV - SDMO - KOHLER | 352 kW 440 kVA

V440C2 IV - SDMO - KOHLER | 352 kW 440 kVA

Worldwide Warranty
Quick Shipping
24/7 Support
SKU:
V440C2 IV
Availability:
IN STOCK, Same day shipping Worldwide available
EPA Compliant:
Export Only
Power Ratings:
352KW 440KVA Standby / 320KW 400KVA Prime
Condition:
Brand New, 2 Years International Warranty
Quality:
Load bank tested and ISO9001 certified
Reliability:
100% Made in USA and Europe (0% China)

OVERVIEW

V440C2 IV - SDMO - KOHLER | 352 kW 440 kVA Diesel Generator

The V440C2 IV - SDMO - KOHLER | 352 kW 440 kVA is an industrial diesel generator set built for dependable standby and prime power. It pairs a Volvo engine with a brushless alternator to deliver stable output for demanding commercial and industrial sites.

  • Standby power (ESP): 352 kWe / 440 kVA
  • Prime power (PRP): 320 kWe / 400 kVA
  • Engine: Volvo TAD1344GE, 6 cylinders in line, turbocharged
  • Alternator: AT01741T, three phase, 4 pole
  • Frequency and voltage: 50 Hz, 400/230 V
  • Engine speed: 1500 RPM
  • Performance class: G3
  • Standby amps: 635 A at 400/230 V
  • Fuel tank capacity: 470 L
  • Control panel: TELYS standard, APM802 optional
  • Version: Enclosed (Fully Weather Proof Silent Enclosure)
  • EPA Compliant: Non-EPA Export Only

Ratings follow ISO 8528-1 and are stated at 25°C air inlet temperature and 100 kPa barometric pressure. Multiple voltage configurations are available, from 200/115 V through 415/240 V.

Volvo Engine Performance and Fuel Efficiency

At the core of this generator set is the Volvo TAD1344GE, a 12.78 liter engine with air to air charge cooling. Its electronic governor holds frequency regulation to within +/- 0.5%, which protects sensitive loads from fluctuation.

  • Fuel consumption at 100% load: 83.10 L/h
  • Fuel consumption at 75% load: 63.30 L/h
  • Fuel consumption at 50% load: 42.80 L/h
  • Maximum standby power at rated RPM: 399 kW
  • Oil capacity: 36 L

These figures give operators a clear basis for planning run time and refueling intervals. The radiator and mechanical fan are designed for a wiring temperature of up to 48/50°C, and the unit is delivered with oil and coolant rated to -30°C.

V440C2 IV - SDMO - KOHLER | 352 kW 440 kVA Alternator Characteristics

The AT01741T alternator is a single bearing, direct coupled design with no collar or brush, which reduces wear parts and routine maintenance. AVR regulation keeps voltage steady as loads change.

  • Insulation class: H
  • Efficiency at 100% load: 93.10%
  • Total harmonic distortion: under 1.5% at no load, under 2% on load
  • Protection rating: IP 23
  • Unbalanced load acceptance ratio: 70%
  • Motor starting capacity: 729 kVA

Low harmonic distortion makes this unit a sound match for electronics, drives, and other equipment that needs clean power. A 500 ms recovery time after a 20% transient voltage dip helps the set respond quickly when large loads come online.

Control Panel Options for Simple Operation

The standard TELYS control unit combines a large display screen, buttons, and a scroll wheel for easy menu navigation. It gives operators the information they need at a glance, without specialized training.

  • Electrical measurements: voltmeter, frequency meter, ammeter
  • Engine parameters: hours counter, oil pressure, coolant temperature, fuel level, engine speed, battery voltage
  • Alarms and faults: oil pressure, coolant temperature, failure to start, overspeed, emergency stop
  • Communication: remote control and operation software, USB and PC connections

For multi-set installations, the optional APM802 system adds a full touch screen interface designed for power plant management. Its customization function complies with IEC 61131-3, and it suits hospitals, data centers, and industrial sites.

V440C2 IV - SDMO - KOHLER | 352 kW 440 kVA Dimensions and Enclosure Options

This generator set is offered as a compact open unit or with a sound attenuated enclosure, so it can be matched to the installation site. Each version is built on a mechanically welded chassis with antivibration suspension.

  • Compact version: 3160 x 1340 x 1805 mm, 3110 kg dry weight
  • M228 enclosure: 4475 x 1410 x 2430 mm, 4080 kg dry weight
  • M228 DW containment: 4527 x 1410 x 2700 mm, 4740 kg dry weight, 1368 L tank
  • Enclosed sound level: as low as 68 dB(A) at 7 meters

The M228 DW version nearly triples fuel capacity for extended run time between fills. Standard equipment also includes a main line circuit breaker, a 24 V charge alternator and starter, and a starting battery with charger.