OVERVIEW
65KW 81KVA PERKINS POWERED DIESEL GENERATOR SET, BRAND NEW
QUALITY: 
100% DESIGNED, ENGINEERED, ASSEMBLED AND TESTED IN ISO9001 AND CE CERTIFIED FACILITIES
 
POWER RATINGS: 
65KW (81KVA) STANDBY, 60KW (75KVA) PRIME, 3PHASES, 0.8PF, 60HZ, XXXV 
 
EMISSIONS COMPLIANCE: 
U.S. EPA TIER 3 compliant engine for Stationary Emergency application as per current U.S. Environmental Protection Agency regulations
POWERED BY A HEAVY DUTY INDUSTRIAL ENGINE FOR MAXIMUM DURABILITY, EXCELLENT RELIABILITY AND WORLDWIDE SUPPORT: 
-PERKINS 1104D-E44TG1, 1800RPM, Turbocharged 
-Electronic governor 
-Industrial-grade cooling system with fan guards and coolant drain extension with in-line valve 
 
PREMIUM INDUSTRIAL-GRADE ALTERNATOR: 
-STAMFORD UCI 224F, 12 Leads, brushless
-Full load rated with thermo-magnetic switch protection 
-Skewed rotor and 2/3 pitch winding suppress triple harmonics and guarantee a superior voltage waveform 
-Class H Insulation and Self-ventilated drip-proof design 
-Electronic automatic voltage regulation 
 
ADVANCED DIGITAL CONTROLLER: 
- DEEP SEA ELECTRONIC DSE4520MKII, Microprocessor based generator controller, UL listed.
- User-friendly, 4-line back light LCD icon display, with on-screen line-diagram functionality.
- Manual and Auto Operation Mode, with 2-wire remote start/stop capability.
- 50 event log & 50+ Engine/ECU/Alternators alarms. Warning, Electrical Trip and Shutdown Alarms.
 
59-GAL SINGLE-WALLED INTEGRAL METALLIC FUEL TANK FOR DAILY AUTONOMY:
- 13-hours runtime autonomy @ 75% PRP, 12-hours runtime autonomy @ 100% PRP 
- Electronic fuel level sender and visual gauge 
- Programmable low-level, high-level alarms and shutdowns
VERSATILE CONFIGURATION IS FULLY PACKAGED AND READY FOR MOST STANDBY AND PRIME POWER APPLICATIONS: 
-7ga, heavy duty mechanically-welded steel skid
-Master cabinet with mechanically-compartmentalized housing for all control/power/breaker/connections components and vertical conduit access
-Main line breaker, 3 pole, set mounted, wired and maximum output rated for complete protection 
-Heavy-duty AVM’s isolate engine/radiator/generator from frame to reduce vibration and noise 
-Electrolyte-charged battery with rack, cables and rubber-booted connections 
-Oil drain extension with in-line valve 
 
ENGINEERED TO THE HIGHEST STANDARDS AND FOR MAXIMUM PEACE OF MIND: 
-QUALITY: Each unit prototype and individually factory load bank tested prior to shipping in ISO9001 Quality facilities
-INTERNATIONAL WARRANTY: up to 2 years or 2000 hours comprehensive international warranty coverage, T&C’s apply 
-PERFORMANCE: The generator accepts 100% rated load in one step as per NFPA110 and meets ISO8528-5 class G-2 for transient response 
-DESIGNED TO INTERNATIONAL STANDARDS: ISO9001; ISO 8528, 3046, 7637; EN 61000-6-3, 61000-6-2, 55011; NEMA ICS 10, MG1, AB1; NEC 700, 701, 702; IEC 60034-1:2017 
-NFPA COMPLIANT: NFPA 37 and NFPA Type 10 Level 1 capable (when equipped with the necessary accessories)
 
             
                     
                     
                     
                     
                     
                     
                    